ADC-T3000 / ADC-T2000 — Heating & Cooling Troubleshooting Guide
Quick checks, wiring/jumper fixes, compressor delays, and advanced diagnostics for heat, cool, and fan problems.
Understand the reported behavior
Common heat issues
- Heat doesn’t turn on / system not heating
- Heat pump not running
- AUX heat not working
- Fan problems during heat
Common cooling issues
- A/C won’t turn on / not cooling
- Heat pump not running
- Fan problems during cool
Fan-only issues
- Fan not running
- Fan starts too early
- Fan on/off with heat incorrectly
Identify your system type
Conventional (normal)
Furnace, boiler, steam/hot-water radiators, radiant floor.
Expected wires: R / RH / RC Y / Y2 W / W2 G
Heat pump
Air-source or geothermal. Outdoor unit provides heat & cool via reversing valve.
Expected wires: R / RH / RC Y / Y2 W / W2 / AUX / E O or B G
Most heat pumps use O. Ruud/Rheem often use B.
Pre-troubleshooting checks
- Test at the thermostat locally (rule out panel/cloud).
- Mode is correct; setpoint is above room temp for heat / below for cool (beyond swing by ≥1°).
- Did anything change recently? (wiring, equipment, power, filters)
- Confirm thermostat and HVAC both have power.
Basic steps & quick wins
Z-Wave enrollment
- Enroll via Add mode on the hub; then Menu → Settings → Network → Add on the stat.
- GC2e requires firmware 1.22+ for ADC-T3000.
Clicks & delays
- T2000 clicks when relays close; T3000 is silent.
- Compressor delay ~5 minutes for cool (and HP heat). Wait out the delay before retesting.
Jumper logic
Stat | R wiring | What to do |
---|---|---|
ADC-T3000 | Single R | Land on RC or RH; choose it in setup (digital jumper). |
ADC-T3000 | Both RC & RH | Select both in setup (no jumper needed). |
ADC-T2000 | Single R | Use physical jumper between RC & RH. |
ADC-T2000 | Both RC & RH | Remove jumper or you’ll blow a fuse/transformer. |
Battery & screen
- Flashing amber buttons + dark screen = batteries critically low → replace immediately.
- Screen won’t stay lit indefinitely. Enable Motion Wake (AC power only).
Targeted fixes by symptom
No heat / not heating
- Wait out compressor delay (HP); set 2°F beyond and retest.
- Verify W on conventional; O/B config on heat pumps.
- Set Heat Type to Electric to force fan (forced air).
- Check jumper (see table) and wire seating.
No cool / not cooling
- Wait out compressor delay; set 2°F below and retest.
- Verify Y call present and wire fully seated.
- On HP, ensure O vs B isn’t reversed.
Heat pump heating vs cooling backwards
- Swap reversing-valve assignment: move wire between O and B and reconfigure.
AUX heat not working
- Confirm AUX exists and is enabled; not in staging delay.
- Check W/W2 placement (AUX is usually W).
Fan issues
- Fan too early / not expected → set Heat Type correctly (Electric vs Fossil).
- Fan not running → verify G wire seated and jumper logic.
- Consider compressor delay or Fan Duty Cycle timing.
System Protect / Safety Delay
- Short-cycle protection (5 min). Frequent triggers: move R to RC (cooling) and reconfig, or install isolation relay.
Advanced diagnostics
Manual wire checks
- Strip ~1/4" straight; fully seat; light pressure on release tab when inserting.
- Tug-test each suspect conductor.
Multimeter (ADC-T2000)
- For C/Y/Y2/G/O-B: Red on RC, black on target terminal → expect 18–30 VAC.
- For Z/W2/W: Red on RH, black on target terminal → 18–30 VAC.
- 0 V → missing power feed (R/jumper) or open circuit; re-strip/re-seat.
Bypass auto wire detection (T3000)
- Menu → Settings → Installer → Continue → Reconfig → Yes
- Select RH only / RC only / RH & RC
- On wiring screen choose No → Bypass and set manually
Special messages
- Power Resistor Required → install 1000 Ω, ½ W across zone valve terminals 1–2 (hydronic).
- Isolation relay required → overcurrent on W/Y/G; isolate (e.g., Emerson 90-380) or call HVAC.